Beschreibung
- FUNCTIONS: Used to protect power distribution facilities from overload and short circuit damage, and can also be used for control and insulation.
- Fast Travel: The electromagnetic travel system can move immediately when the circuit is short circuits to maintain the safety of the circuit.
- ARC INME: DC arc deflation is harder than AC. This DC mini circuit breaker has a magnetic system that helps to deflate arc.
- APPLICATION: Used in DC power system, ship electric power system, solar photovoltaic system or other DC systems.
- INSTALLATION: Screw clamp wires, 35mm DIN rail mount.
Main product name: DZ47Z-63 Product type: DC Miniature circuit breaker Rated working voltage: 1000V DC Rated current [In]: 10A 16A 20A 25A 32A 40A 50A 63A Poles: 2 P motion unit technology: Thermal-magnetic curve code: C breaking capacity: 4kA Ics=Icu Complementary Nominal impact resistance voltage [Uimp]: 4 kV mechanical strength: 10000 cycles electrical resistance: 2000 cycles Mounting support: 35mm DIN rail net weight: 0.180kg tightening torque: 2.5 N.m standard: IEC60947-2 Operating temperature: -56°F (-25℃) ~ 142°F (60℃) Assembly tips Pay attention to polarity. Choose the cable size according to the rated current. Package includes: 1 x DC miniature circuit breaker 1 x DIN rail 2 x screws.
Häufige Fragen